Maximum Pressure Maximum Pressure |
---|
|
For Use With For Use With |
---|
|
|
Housing Material Housing Material |
---|
|
Connection Material Connection Material |
---|
|
Specifications Met Specifications Met |
---|
|
Wire Connection Type Wire Connection Type |
---|
|
Environment Environment |
---|
|
|
Relay Current Relay Current |
---|
|
More
Remotely monitor pressure in general purpose applications such as pumping and compressing systems. These transmitters, also known as transducers, convert pressure to an electrical signal that can be interpreted by receiving devices, such as remote displays, programmable logic controllers, and motor speed controls. For your receiving device to interpret the signal from the transmitter, you will need to calibrate it for the transmitter's pressure range and output signal. As pressure increases, the output signal from the transmitter will increase. Transmitters will only provide accurate readings within the rated pressure range. Maximum pressure is the maximum spike in pressure a transmitter can withstand without damage.
To view transmitter wiring diagrams, select a part number and click Product Detail.
4-20mA current output transmitters connect using two wires. The same wire is used to send a signal to the receiver and to power the transmitter. Current doesn’t lose signal over long distances and isn’t affected by electrical interference from other devices.
DC voltage output transmitters connect using three wires—two wires into the power supply and a separate wire that sends a signal to the receiver. The receiver and the transmitter share a common ground wire back to the power supply.
Transmitters with calibration certificate traceable to NIST include documentation that states they've passed a test for accuracy.
Transmitters that are rated IP67 and NEMA 4X are good for washdown and corrosive environments.
Transmitters with an M12 plug connection are commpatible with M12 sockets.
Pressure Range, psi | Max. Pressure, psi | Input Voltage | Pipe Size | For No. of Wires | Ht. | Wd. | Environmental Rating | Each | |
0-30 | 300 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 0000000 |
0-50 | 500 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-100 | 1,000 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-300 | 3,000 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-1,000 | 10,000 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-1,500 | 7,500 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-3,000 | 15,000 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
0-10,000 | 24,000 | 9-36V DC | 1/4 | 2 | 2 5/8" | 15/16" | IP67, NEMA 4X | 00000000 | 000000 |
Pressure Range, psi | Max. Pressure, psi | Input Voltage | Pipe Size | For No. of Wires | Electrical Connection Thread Size | Ht. | Wd. | Each | |
Transmitters | |||||||||
---|---|---|---|---|---|---|---|---|---|
0-10,000 | 12,000 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 0000000 |
Transmitters with Calibration Certificate Traceable to NIST | |||||||||
0-30 | 60 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-50 | 100 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-60 | 120 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-100 | 200 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-200 | 400 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-300 | 600 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-500 | 1,000 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-1,000 | 2,000 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-5,000 | 7,500 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-10,000 | 12,000 | 9-36V DC | 1/4 | 2 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
Pressure Range, psi | Max. Pressure, psi | Input Voltage | Pipe Size | For No. of Wires | Electrical Connection Thread Size | Ht. | Wd. | Each | |
Transmitters | |||||||||
---|---|---|---|---|---|---|---|---|---|
0-15 | 30 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 0000000 |
0-30 | 60 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-50 | 100 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-60 | 120 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-100 | 200 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-200 | 400 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-300 | 600 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-500 | 1,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-1,000 | 2,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-1,500 | 3,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-3,000 | 6,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-10,000 | 12,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
Transmitters with Calibration Certificate Traceable to NIST | |||||||||
0-15 | 30 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-30 | 60 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-50 | 100 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-60 | 120 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-100 | 200 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-200 | 400 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-300 | 600 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-500 | 1,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-1,000 | 2,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 0000000 | 000000 |
0-1,500 | 3,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-3,000 | 6,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-5,000 | 7,500 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
0-10,000 | 12,000 | 14-36V DC | 1/4 | 3 | PG-9 | 2 5/8" | 1 3/8" | 00000000 | 000000 |
Read pressure directly at the source and send data remotely with one device. Also known as transducers, these transmitters convert pressure to an electrical signal that can be interpreted by receiving devices, such as remote displays, programmable logic controllers, and motor speed controls to monitor pressure or control equipment. As pressure increases, the output signal from the transmitter will increase. For your receiving device to interpret the signal from the transmitter, you will need to calibrate it for the pressure range and output signal of the transmitter. Transmitters will only provide accurate readings within the rated pressure range. Maximum pressure is the maximum spike in pressure a transmitter can withstand without damage. All transmitters are rated IP67 for protection from temporary submersion in washdown environments. They’re CE marked as compliant with European health, safety, and environmental standards.
All of these transmitters connect using two wires to send a 4-20mA current output. The same wire is used to send a signal to the receiver and to power the transmitter. Current doesn’t lose signal over long distances and isn’t affected by electrical interference from other devices. Some also connect using three wires to send a DC voltage output—two wires into the power supply and a separate wire that sends a signal to the receiver. The receiver and the transmitter share a common ground wire back to the power supply.Transmitters are commpatible with M12 sockets.
For technical drawings and 3-D models, click on a part number.
Pressure Range, psi | Max. Pressure, psi | Input Voltage | Pipe Size | For No. of Wires | Ht. | Wd. | Environmental Rating | Specifications Met | Each | |
4-20mA Current Output—M12 Plug Connection | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
0-5,800 | 14,500 | 18-36V DC | 1/4 | 2 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 0000000 |
0-10V DC Voltage Output—4-20mA Current Output—M12 Plug Connection | ||||||||||
0-25 | 145 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-70 | 200 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-140 | 500 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-290 | 1,000 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-700 | 2,175 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-1,400 | 4,350 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-3,600 | 10,800 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-5,800 | 14,500 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-8,700 | 14,500 | 18-36V DC | 1/4 | 1 | 3 3/4" | 1 7/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-10V DC Voltage Output—M12 Plug Connection | ||||||||||
0-25 | 145 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-290 | 1,000 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-700 | 2,175 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-3,600 | 10,800 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-5,800 | 14,500 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
0-8,700 | 14,500 | 18-36V DC | 1/4 | 3 | 4 13/16" | 1 3/8" | IP67 | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
Monitor pressure from a distance with these remote displays. They support five different input mA current and DC voltage signals, so they can be used with most common transmitters. Settings are saved even when power is turned off. To prevent tampering, they have a lockout feature that requires a password to modify settings. They are rated NEMA 4X for protection from corrosion and washdowns.
The display with two SPDT (single pole, double throw) relays can be used to send control signals for process-control systems.
Input Signal | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Input AC Voltage | Transmitter Power Supply | No. of Signal Inputs | Current, mA | Voltage | Selection | Relay Current | For DIN Panel Cutout Size | Environmental Rating | Each | |
With Lockout, USB Cable | ||||||||||
85-265V AC | 24V DC | 1 | 0-20, 4-20 | 0-5V DC, 0-10V DC, 1-5V DC | Switch | __ | 1/8 | NEMA 4X | 00000000 | 0000000 |
With Two SPDT (Single Pole, Double Throw) Relays, Alarm LED Indicator, Lockout, USB Cable | ||||||||||
85-265V AC | 24V DC | 1 | 0-20, 4-20 | 0-5V DC, 0-10V DC, 1-5V DC | Switch | 3 A @ 120 V AC, 3 A @ 240 V AC | 1/8 | NEMA 4X | 00000000 | 000000 |