Fixed-Setpoint Threaded Temperature Switches

Set to actuate at a specific temperature, these switches are easy to setup and prevent changes to the setpoint. They have a threaded probe, so they install directly into tanks, pipelines, and other process components to turn equipment on and off at a set temperature.
Narrow differential switches reset after a small temperature change in the opposite direction of your switch's actuation. For example, in a rising-actuation switch, they reset after the temperature falls 3° below the setpoint. Use them in systems where temperature changes slowly and where you need precision. Wide differential switches reset after the temperature significantly decreases (approximately 15%) below the setpoint. Use them in systems that cannot handle frequent power cycling.
Rising actuation switches activate when the temperature rises to the setpoint and then reset when the temperature falls below the setpoint. Choose rising actuation SPST-NO switches to power a cooler or trigger an alarm. Choose rising actuation SPST-NC switches to turn off a heater or other equipment when the temperature rises to the setpoint.
Falling actuation switches activate when the temperature falls to the setpoint and then reset when the temperature rises above the setpoint. Choose falling actuation SPST-NO switches to power a heater or activate an alarm. Choose falling actuation SPST-NC switches to turn off a cooler or other equipment when the temperature falls to the setpoint.
All switches are NEMA 4 and 13 rated to seal out dirt, oil, and water from washdowns. IP67 rated switches stand up to temporary submersion. UL and C-UL listed switches meet U.S. and Canadian safety standards.
For technical drawings and 3-D models, click on a part number.
Probe | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Actuation Point, °F | Actuation Tolerance | Approx. Difference Between Setpoint and Reset Point, °F | Max. Switching Current @ Voltage (Electrical Phase) | Dia. | Lg. | Max. Pressure, psi | Environmental Rating | Specifications Met | Each | |
SPST-NO | ||||||||||
Threaded Brass Probe—1/2 NPT Male | ||||||||||
Narrow Differential Range Sensitivity—Rising Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 000000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Narrow Differential Range Sensitivity—Falling Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Wide Differential Range Sensitivity—Rising Actuation | ||||||||||
50° | ±7° F | 8° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
75° | ±7° F | 12° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
100° | ±7° F | 15° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
125° | ±7° F | 19° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
150° | ±7° F | 23° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
175° | ±7° F | 27° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
200° | ±7° F | 30° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
225° | ±7° F | 34° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
250° | ±7° F | 38° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
275° | ±7° F | 42° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
SPST-NC | ||||||||||
Threaded Brass Probe—1/2 NPT Male | ||||||||||
Narrow Differential Range Sensitivity—Rising Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Narrow Differential Range Sensitivity—Falling Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Wide Differential Range Sensitivity—Rising Actuation | ||||||||||
50° | ±7° F | 8° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
75° | ±7° F | 12° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
100° | ±7° F | 15° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
125° | ±7° F | 19° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
150° | ±7° F | 23° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
175° | ±7° F | 27° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
200° | ±7° F | 30° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
225° | ±7° F | 34° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
250° | ±7° F | 38° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
275° | ±7° F | 42° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
Surface-Mount Temperature Switches

Often used to control heat cable output, these switches maintain your surface’s temperature by turning equipment on or off when they reach a set temperature. They actuate when the temperature rises to the setpoint and reset when the temperature falls below the reset point. Since they're SPDT (single pole, double throw) switches, they control one circuit and can either be wired to turn one device from on to off (normally closed) or from off to on (normally open). Wire them normally closed to power a heater—when the temperature rises to the setpoint, the heater will turn off until the temperature falls below the reset point. Or wire them normally open to turn on alarms or other devices when the temperature rises above the setpoint. Their setpoint isn’t adjustable, so they’re easy to set up and there’s no risk of unintentional changes.
CSA and CSA-US certified, they meet Canadian and American safety standards.
For technical drawings and 3-D models, click on a part number.
Mounting Holes | SPDT | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Actuation Point, °F | Actuation Tolerance | Approx. Difference Between Setpoint and Reset Point, °F | Max. Switching Current @ Voltage (Electrical Phase) | Ht. | Wd. | No. of | Dia. | Specifications Met | Each | |
Nonadjustable Rising Actuation Point | ||||||||||
47° | ±6° F | 10° | 15 A @ 240 V AC (Single) | 1 1/8" | 2" | 2 | 3/16" | CSA Certified, CSA-US Certified | 0000000 | 0000000 |
60° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 1 1/8" | 2" | 2 | 3/16" | CSA Certified, CSA-US Certified | 0000000 | 000000 |
75° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 1 1/8" | 2" | 2 | 3/16" | CSA Certified, CSA-US Certified | 0000000 | 000000 |
105° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 1 1/8" | 2" | 2 | 3/16" | CSA Certified, CSA-US Certified | 0000000 | 000000 |
200° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 1 1/8" | 2" | 2 | 3/16" | CSA Certified, CSA-US Certified | 0000000 | 000000 |
Harsh Environment Surface-Mount Temperature Switches

An airtight seal on these switches blocks out dust, dirt and moisture. They maintain your surface’s temperature by turning equipment on or off when they reach a set temperature. These switches actuate when the temperature rises to the setpoint and reset when the temperature falls below the reset point. Since they're SPDT (single pole, double throw) switches, they control one circuit and can either be wired to turn one device from on to off (normally closed) or from off to on (normally open). Wire them normally closed to power a heater—when the temperature rises to the setpoint, the heater will turn off until the temperature falls below the reset point. Or wire them normally open to turn on alarms or other devices when the temperature rises above the setpoint. Their setpoint isn’t adjustable, so they’re easy to set up and there’s no risk of unintentional changes.
CSA-US and CSA certified, they also meet American and Canadian safety standards.
For technical drawings and 3-D models, click on a part number.
Mounting Holes | SPDT | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Actuation Point, °F | Actuation Tolerance | Approx. Difference Between Setpoint and Reset Point, °F | Max. Switching Current @ Voltage (Electrical Phase) | Ht. | Wd. | No. of | Dia. | Specifications Met | Each | |
Nonadjustable Rising Actuation Point | ||||||||||
47° | ±6° F | 10° | 15 A @ 240 V AC (Single) | 2 15/16" | 2" | 2 | 11/64" | CSA-US Certified, CSA Certified | 00000000 | 0000000 |
60° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 2 15/16" | 2" | 2 | 11/64" | CSA-US Certified, CSA Certified | 00000000 | 000000 |
75° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 2 15/16" | 2" | 2 | 11/64" | CSA-US Certified, CSA Certified | 00000000 | 000000 |
105° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 2 15/16" | 2" | 2 | 11/64" | CSA-US Certified, CSA Certified | 00000000 | 000000 |
200° | ±6° F | 15° | 15 A @ 240 V AC (Single) | 2 15/16" | 2" | 2 | 11/64" | CSA-US Certified, CSA Certified | 00000000 | 000000 |
Enclosure Thermostats

Control a single heating or cooling device in your enclosure to keep electronics at a safe operating temperature. Clip them on to a DIN rail and connect them to your heater, fan, or air conditioner.
All these thermostats meet American, Canadian, or European safety standards. They have an IP20 rating—to prevent shocks, fingers won’t fit inside. They also meet UL 94 V-0, so they self-extinguish within 10 seconds if they catch fire and won’t spread the fire by dripping.
Nonadjustable thermostats have a fixed temperature setting to prevent tampering or accidental changes.
These thermostats keep the air in your enclosure within a set range. Temperature setting is the high end of the range for both heating and cooling thermostats. Heating thermostats are normally closed—when the air in your enclosure reaches the temperature setting, the thermostat will turn the heater off. Cooling thermostats are normally open, so they’ll switch your fan or air conditioner on when the air in your enclosure reaches the temperature setting.
Temperature difference is the difference between the temperature when the thermostat turns your device on and when it turns off. For a heater thermostat with a temperature setting of 50° and an 18° temperature difference, the thermostat will switch your heater on when the temperature goes below 32° and off once the temperature reaches 50°. Thermostats with a lower temperature difference maintain a narrower range of temperatures, but they use more power because they switch on and off more frequently.
Temperature | Overall | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Setting | Difference | Tolerance | Voltage | Current, A | For DIN Rail Ht., mm | Ht. | Wd. | Dp. | Environmental Rating | Specifications Met | Each | |
For Cooling | ||||||||||||
Nonadjustable | ||||||||||||
95° F/35° C | 18° F/10° C | ±11° F/±6° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 000000 |
122° F/50° C | 18° F/10° C | ±11° F/±6° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 00000 |
140° F/60° C | 18° F/10° C | ±12.6° F/±7° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 00000 |
For Heating | ||||||||||||
Nonadjustable | ||||||||||||
50° F/10° C | 18° F/10° C | ±9° F/±5° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 00000 |
59° F/15° C | 18° F/10° C | ±9° F/±5° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 00000 |
77° F/25° C | 18° F/10° C | ±9° F/±5° C | 120V AC/240V AC 24V DC to 75V DC | 16 | 35 | 1 7/8" | 1 5/16" | 1 5/16" | IP20 | CE Marked, UL 94 V-0, UL Recognized Component, C-UL Recognized Component, VDE Certified | 0000000 | 00000 |
Enclosure Thermostats for Multiple Devices

Keep electronics in your enclosure from getting too hot or cold with these thermostats that control two devices at once. Clip them to a DIN rail to install.
Nonadjustable thermostats prevent tampering and accidental changes.
Heating and cooling thermostats control heaters and fans or air conditioners.
Heating and cooling thermostats with two actuation points control two devices independently. When your enclosure temperature is within the set range, neither device is powered, so they’re more efficient than changeover thermostats. For each device, temperature setting is the high end of the temperature range, and temperature difference is the size of the range. For a thermostat with temperature settings of 59° and 95° F and an 18° F temperature difference, the heater will switch on when your enclosure is colder than 41° F and turn off when it reaches 59° F. The fan or other cooling device will switch on when the temperature goes above 95° F and turn off once the enclosure cools to 77° F.
Cooling thermostats regulate two cooling devices, such as a fan and an air conditioner, for two-stage cooling. Use only one device for cooling in mild temperatures or both for extreme heat. These thermostats switch your equipment on when the enclosure is hotter than the temperature setting. Once the temperature is reduced by the temperature difference, it will switch off. For example, a thermostat set at 77° F for a fan and 140° F for an air conditioner will power both devices when the enclosure is over 140° F. With a temperature difference of 18° F, the air conditioner will switch off when the temperature goes below 122° F. The fan will run until the temperature reaches 59° F, and switch back on if it heats up to 77° F or hotter.
All thermostats meet IP20, which means they’re designed so fingers can’t fit inside and get shocked. They also meet UL 94 V-0, so they self-extinguish within 10 seconds if they catch on fire and won’t spread the fire by dripping. Thermostats that are CE marked or VDE certified meet European safety standards. UL Recognized Component and C-UL Recognized Component thermostats also meet American and Canadian safety standards.
Heating Temperature | Cooling Temperature | Overall | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Setting | Difference | Tolerance | Setting | Difference | Tolerance | Voltage | Ht. | Wd. | Dp. | Environmental Rating | Specifications Met | Each | |
Nonadjustable | |||||||||||||
59° F/15° C | 18° F/10° C | ±9° F/±5° C | 95° F/35° C | 18° F/10° C | ±12.6° F/±7° C | 120V AC/240V AC 24V DC to 75V DC | 1 7/8" | 2 1/2" | 1 5/16" | IP20 | CE Marked, UL Recognized Component, C-UL Recognized Component, UL 94 V-0, VDE Certified | 0000000 | 000000 |
59° F/15° C | 18° F/10° C | ±9° F/±5° C | 122° F/50° C | 18° F/10° C | ±12.6° F/±7° C | 120V AC/240V AC 24V DC to 75V DC | 1 7/8" | 2 1/2" | 1 5/16" | IP20 | CE Marked, UL Recognized Component, C-UL Recognized Component, UL 94 V-0, VDE Certified | 0000000 | 00000 |
77° F/25° C | 18° F/10° C | ±9° F/±5° C | 122° F/50° C | 18° F/10° C | ±12.6° F/±7° C | 120V AC/240V AC 24V DC to 75V DC | 1 7/8" | 2 1/2" | 1 5/16" | IP20 | CE Marked, UL Recognized Component, C-UL Recognized Component, UL 94 V-0, VDE Certified | 0000000 | 00000 |
Cooling Temperature | Cooling Temperature | Overall | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Setting | Difference | Tolerance | Setting | Difference | Tolerance | Voltage | Ht. | Wd. | Dp. | Environmental Rating | Specifications Met | Each | |
Nonadjustable | |||||||||||||
122° F/50° C | 18° F/10° C | ±12.6° F/±7° C | 140° F/60° C | 18° F/10° C | ±12.6° F/±7° C | 120V AC/240V AC 24V DC to 75V DC | 1 7/8" | 2 1/2" | 1 5/16" | IP20 | CE Marked, VDE Certified, C-UL Recognized Component, UL 94 V-0, UL Recognized Component | 0000000 | 000000 |