Fire-Stop Caulk





Easy to apply and quick to set, this caulk is a popular choice for sealing small openings in fire-resistant walls and floors. It’s often used to line seams or fill gaps around cables or pipes that run between rooms. You can use it alone or with other fire-stop products. This caulk is tested to ASTM and UL standards for stopping the spread of smoke and flames. It resists vibration, so it will flex with movement rather than crack or pull away from surfaces. Apply with a caulk gun or trowel.
Spray-on caulk is used to evenly coat hard-to-reach openings. It’s often used to seal the spaces where fire-rated walls, floors, and ceilings meet.
Acrylic caulk is water-based, which is the most common formula for fire-stop caulk. It’s a good choice for most applications. Expandable caulk is used to seal the area around PVC pipes, cables, and other equipment that can melt or shrink during a fire. When it’s heated, it expands to fill gaps.
Silicone caulk forms a watertight, flexible seal. Use it to seal openings that are exposed to weather, washdowns, or standing water.
| Container Size | Application Temperature, °F | Color | Fire Rating, hrs. | Flammability Rating | Specifications Met | Each | |
Caulk | |||||||
|---|---|---|---|---|---|---|---|
Acrylic | |||||||
| 10.3 fl. oz. Cartridge | 40° to 120° | Red | 4 | ASTM E84 10/0 for Flame and Smoke, UL 723 10/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 0000000 | 000000 |
| 30 fl. oz. Cartridge | 40° to 120° | Red | 4 | ASTM E84 10/0 for Flame and Smoke, UL 723 10/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 0000000 | 00000 |
Acrylic—Expandable | |||||||
| 10.3 fl. oz. Cartridge | 40° to 120° | Red | 4 | ASTM E84 0/0 for Flame and Smoke, UL 723 0/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, ASTM G21, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 00000 |
| 30 fl. oz. Cartridge | 40° to 120° | Red | 4 | ASTM E84 0/0 for Flame and Smoke, UL 723 0/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, ASTM G21, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 00000 |
| 5 gal. Pail | 40° to 120° | Red | 4 | ASTM E84 0/0 for Flame and Smoke, UL 723 0/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, ASTM G21, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 000000 |
Silicone—Watertight | |||||||
| 10.1 fl. oz. Cartridge | -20° to 120° | Gray | 3 | ASTM E84 3/22 for Flame and Smoke, UL 723 3/22 for Flame and Smoke | ASTM C920, ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1399, ASTM E1966, UL 2079, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 00000 |
| 20.2 fl. oz. Stick | -20° to 120° | Gray | 3 | ASTM E84 3/22 for Flame and Smoke, UL 723 3/22 for Flame and Smoke | ASTM C920, ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1399, ASTM E1966, UL 2079, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 00000 |
| 4.5 gal. Pail | -35° to 140° | Gray | 4 | ASTM E84 5/45 for Flame and Smoke, UL 723 5/45 for Flame and Smoke | ASTM C920, ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1399, ASTM E1966, UL 2079, ASTM G21, FM Approved, CAN/ULC-S115 | 00000000 | 000000 |
Spray-On Caulk | |||||||
Acrylic | |||||||
| 5 gal. Pail | 40° to 120° | Red | 3 | ASTM E84 0/0 for Flame and Smoke, UL 723 0/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, ASTM G21, FM Approved, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115 | 00000000 | 000000 |
Fire-Stop Putty
![]() | ![]() Pad |
![]() Stick |
Hand-mold this putty into small openings in fire-resistant walls and floors. Often used to seal the area around PVC pipes or cables, it expands when heated to fill the gaps left if your equipment melts. It’s tested to ASTM and UL standards to stop the spread of smoke and flames.
Putty pads are often used to seal the area around electrical boxes. Mold them onto the sides of the box before installing it in a wall or floor.
| Form | Lg. | Wd. | Thick. | Color | Application Temperature, ° F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Each | |
| Pad | 7" | 7" | 1/8" | Red | 40° to 120° | 3 | ASTM E84 10/125 for Flame and Smoke, UL 723 10/125 for Flame and Smoke | ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 0000000 | 00000 |
| Stick | 10" | 1 1/2" | 1 1/2" | Red | 40° to 120° | 3 | ASTM E84 10/125 for Flame and Smoke, UL 723 10/125 for Flame and Smoke | ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 0000000 | 00000 |
| Form | Lg. | Wd. | Thick. | Color | Application Temperature, ° F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Pkg. Qty. | Pkg. | |
| Pad | 7" | 7" | 1/8" | Red | 40° to 120° | 3 | ASTM E84 10/125 for Flame and Smoke, UL 723 10/125 for Flame and Smoke | ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 20 | 0000000 | 0000000 |
| Stick | 10" | 1 1/2" | 1 1/2" | Red | 40° to 120° | 3 | ASTM E84 10/125 for Flame and Smoke, UL 723 10/125 for Flame and Smoke | ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 12 | 0000000 | 000000 |
Fire-Stop Cement



Seal openings in fire-resistant floors and walls to stop the spread of smoke and flames. Often used to fill gaps around pipes or conduit, this cement forms a rigid, tight-fitting shield. It’s heavier and messier to apply than fire-stop blocks or sheets, but it's an economical choice for covering a large area. You can also paint over this cement once it dries.
This cement comes as a powder—mix in water until you reach the consistency you need. The thicker the cement, the better it will stick to walls; thinner cement dries with a smoother finish on floors.
Cement in a pail is best for small, infrequent jobs. The pail is resealable and has a carrying handle.
Fire-Stop Pipe Collars


Fill the space between plastic pipes and the fire-rated wall or floor they pass through. These collars are tested to ASTM and UL standards for preventing the spread of smoke and flames. They expand when heated, so they’ll fill any gaps left if your pipe melts or shrinks. Slip a collar over the end of your pipe and press into the opening in the wall or floor. If your pipe runs through a wall, seal both sides.
| For Pipe OD | Wd. | Thick. | Material | Fasteners Included | Fire Rating, hrs. | Specifications Met | Each | |
| 1 1/2" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 000000 | 000000 |
| 2" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 000000 | 00000 |
| 3" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 000000 | 00000 |
| 4" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 000000 | 00000 |
| For Pipe OD | Wd. | Thick. | Material | Fasteners Included | Fire Rating, hrs. | Specifications Met | Pkg. Qty. | Pkg. | |
| 1 1/2" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 10 | 000000 | 0000000 |
| 2" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 10 | 000000 | 000000 |
| 3" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 10 | 000000 | 000000 |
| 4" | 1 1/2" | 1/4" | Steel | No | 3 | ASTM E814, UL 1479, CAN/ULC-S115 | 10 | 000000 | 000000 |
Fire-Stop Sheets


Cut these sheets to any size and shape you need to seal large openings in fire-resistant walls and floors. They’re often used to fill the space around pipes, conduit, and ducts. These sheets are tested to ASTM and UL standards for stopping the spread of smoke and flames. Made of steel, they have a firestop coating that expands when it’s heated. If the equipment passing through these panels melts or shrinks during a fire, this coating will fill the gaps.
Use shears to cut these panels to size, then fasten to your surface with No. 10 self-drilling sheet metal screws (not included). Fill any gaps around the sheet with fire-stop caulk (sold separately) for a tight seal. Once they’re installed, you can paint over them without losing fire protection.
Fire-Stop Electrical Box Inserts
Seal electrical boxes to maintain fire-resistant walls. These inserts mount inside electrical boxes to block the spread of smoke and flames. When heated, they expand to seal gaps, such as those left by melted wire. They fit common box sizes.
Use gaskets when cable or switches have already been installed. They sit just inside your cover plate.
Use pads before cable is installed. The adhesive side sticks to the back wall of your electrical box. They can be used only with metallic boxes.


| Industry Designation | For No. of Outlets | For No. of Toggle Switches | Lg. | Wd. | Thick. | Application Temperature, °F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Each | |
For NEMA Outlets | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 Gang | 2 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
| 2 Gang | 4 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
For GFCI Outlets | |||||||||||
| 1 Gang | 1 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
| 2 Gang | 2 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
For Toggle Switches | |||||||||||
| 1 Gang | __ | 1 | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
| 2 Gang | __ | 2 | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
| Industry Designation | For No. of Outlets | For No. of Toggle Switches | Lg. | Wd. | Thick. | Application Temperature, °F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Pkg. Qty. | Pkg. | |
For NEMA Outlets | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 Gang | 2 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 0000000 |
| 2 Gang | 4 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
For GFCI Outlets | ||||||||||||
| 1 Gang | 1 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
| 2 Gang | 2 | __ | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
For Toggle Switches | ||||||||||||
| 1 Gang | __ | 1 | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
| 2 Gang | __ | 2 | 5" | 5" | 1/8" | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |


| Industry Designation | Lg. | Wd. | Thick. | Mount Type | Application Temperature, °F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Each | |
| 1 Gang | 1 13/16" | 2 13/16" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
| 2 Gang | 3 3/4" | 3 11/16" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 0000 |
| 2 Gang | 4 3/8" | 4 3/8" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
| Industry Designation | Lg. | Wd. | Thick. | Mount Type | Application Temperature, °F | Fire Rating, hrs. | Flammability Rating | Specifications Met | Pkg. Qty. | Pkg. | |
| 1 Gang | 1 13/16" | 2 13/16" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 0000000 |
| 2 Gang | 3 3/4" | 3 11/16" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
| 2 Gang | 4 3/8" | 4 3/8" | 1/4" | Adhesive Back | 40° to 120° | 2 | ASTM E84 5/5 for Flame and Smoke, UL 723 5/5 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM G21, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 50 | 00000000 | 000000 |
Fire-Stop Plugs


Squeeze these foam plugs into the ends of pipe or conduit to fill the space around cables. When heated, they expand to fill any gaps left if the cables shrink or melt. They’re tested to ASTM and UL standards for stopping the spread of smoke and flames. Cut holes in these plugs to pass cables through, or use them to block the ends of unused pipe or conduit. Once they’re installed, you can paint them without losing fire protection.
Fire-Stop Blocks


Stack these blocks around cables or pipes that run through fire-rated walls and floors. They’re made from compactible foam, so you can pack them in tightly to create a dense barrier. If a fire breaks out, they expand to seal any remaining gaps. These blocks are tested to ASTM and UL standards for stopping the spread of smoke and flames.
Blocks with hook and loop attachment strips can be locked together or taken apart easily, so they're good for creating temporary barriers. Their cover expands in two directions when exposed to flames. Do not cut these blocks, or they will lose their shape and fail to stop fire and smoke.
Cut-to-size blocks can be customized to fill odd-shaped openings. They expand in all directions when exposed to flames, so you can cut them without reducing their fire protection.
Use fire-stop caulk to seal small gaps between or around the blocks.


| Thick. | Lg. | Wd. | Color | Fire Rating, hrs. | Specifications Met | Each | |
Blocks with Fire-Stop Cover and Hook and Loop Attachment Strips | |||||||
|---|---|---|---|---|---|---|---|
| 2" | 9" | 4" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 00000000 | 000000 |
| 2" | 9" | 6" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
| 3" | 9" | 6" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
Cut-to-Size Blocks | |||||||
| 2" | 8" | 5" | Red | 2 | ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 00000000 | 00000 |
| Thick. | Lg. | Wd. | Color | Fire Rating, hrs. | Specifications Met | Pkg. Qty. | Pkg. | |
Blocks with Fire-Stop Cover and Hook and Loop Attachment Strips | ||||||||
|---|---|---|---|---|---|---|---|---|
| 2" | 9" | 4" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 24 | 00000000 | 0000000 |
| 2" | 9" | 6" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 24 | 00000000 | 000000 |
| 3" | 9" | 6" | Black/Red | 3 | ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 24 | 00000000 | 000000 |
Cut-to-Size Blocks | ||||||||
| 2" | 8" | 5" | Red | 2 | ASTM E119, UL 263, ASTM E814, UL 1479, CAN/ULC-S115, FM Approved | 24 | 00000000 | 000000 |

| Container Size | Application Temperature, °F | Color | Fire Rating, hrs. | Flammability Rating | Specifications Met | Each | |
| 10.3 fl. oz. Cartridge | 40° to 120° | Red | 4 | ASTM E84 10/0 for Flame and Smoke, UL 723 10/0 for Flame and Smoke | ASTM E90, ASTM E119, UL 263, ASTM E814, UL 1479, ASTM E1966, UL 2079, CAN/ULC-S101, CAN/ULC-S102, CAN/ULC-S115, FM Approved | 0000000 | 000000 |