About Heaters for Pipes and Tubes
Self-Regulating Heat Cable—Adjusts its heat output in response to surface as well as surrounding temperatures.
Constant-Wattage Heat Cable—Always puts out the designated amount of watts/ft., regardless of the surrounding temperature.
More
Heat Pipes

Protect computers, sensitive electronic components, lighting, injection molders, and HVAC systems from damage by routing heat away from them and toward a heat sink, where the heat can be dissipated. For best results, heat pipes should be soldered to heat sinks and other components. For small jobs and prototypes, however, they can be joined with thermal epoxy. Cooling capacity is the amount of heat that a heat pipe can carry.
Flat heat pipes, often called vapor chambers, can be embedded into your heat sink to spread heat uniformly across the base, helping the heat to dissipate faster.
Heat pipes with a grooved wick transfer heat better than those with a sintered wick, meaning they can carry more heat. They are not good, however, for applications that will require many bends in the pipe. Position them horizontally, since they do not work well against gravity.
Heat pipes with a sintered wick handle high fluctuations in temperature better than those with a grooved wick. They’re also best for applications that will require many bends in the pipe. Position them horizontally or vertically—they work well in both orientations.
Use optional heat pipe benders to create smooth, accurate bends in round heat pipe. These specially designed tools allow a smooth bending motion to reduce marks on your pipe, which ordinary pliers can often leave behind. All have graduation markings to prevent over bending, which can reduce the ability of your heat pipe to transfer heat. Every 45° bend in a heat pipe will reduce the cooling capacity of the heat pipe by about 2.5%. Place these tools on benches, vises, and workstations without scratching them—all have rubber mounting feet.


Heat Pipes | Heat Pipe Benders | |||||||
---|---|---|---|---|---|---|---|---|
Length, mm | Cooling Capacity (Installed Length) | Temperature Range, °F | Material | Working Fluid | Each | Each | ||
Grooved Wick | ||||||||
4 mm OD | ||||||||
200 | 100 Btu/hr. (125 mm), 130 Btu/hr. (100 mm), 90 Btu/hr. (150 mm) | 90° to 245° | Copper | Water | 0000000 | 000000 | 0000000 | 0000000 |
300 | 60 Btu/hr. (200 mm), 90 Btu/hr. (150 mm), 50 Btu/hr. (250 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |
6 mm OD | ||||||||
200 | 170 Btu/hr. (125 mm), 210 Btu/hr. (100 mm), 140 Btu/hr. (150 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |
300 | 130 Btu/hr. (200 mm), 180 Btu/hr. (150 mm), 100 Btu/hr. (250 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |
Sintered Wick | ||||||||
4 mm OD | ||||||||
100 | 210 Btu/hr. (40 mm), 170 Btu/hr. (50 mm), 140 Btu/hr. (60 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
150 | 140 Btu/hr. (60 mm), 110 Btu/hr. (75 mm), 90 Btu/hr. (90 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
200 | 100 Btu/hr. (80 mm), 80 Btu/hr. (100 mm), 70 Btu/hr. (120 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
250 | 80 Btu/hr. (100 mm), 60 Btu/hr. (125 mm), 50 Btu/hr. (150 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
6 mm OD | ||||||||
70 | 650 Btu/hr. (28 mm), 520 Btu/hr. (35 mm), 430 Btu/hr. (42 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
100 | 450 Btu/hr. (40 mm), 360 Btu/hr. (50 mm), 300 Btu/hr. (60 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
150 | 300 Btu/hr. (60 mm), 240 Btu/hr. (75 mm), 200 Btu/hr. (90 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
250 | 180 Btu/hr. (100 mm), 140 Btu/hr. (125 mm), 120 Btu/hr. (150 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
350 | 120 Btu/hr. (140 mm), 100 Btu/hr. (175 mm), 80 Btu/hr. (210 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |
8 mm OD | ||||||||
70 | 940 Btu/hr. (28 mm), 760 Btu/hr. (35 mm), 630 Btu/hr. (42 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
100 | 660 Btu/hr. (40 mm), 530 Btu/hr. (50 mm), 440 Btu/hr. (60 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
150 | 440 Btu/hr. (60 mm), 350 Btu/hr. (75 mm), 290 Btu/hr. (90 mm) | 90° to 245° | Copper | Water | 0000000 | 0000 | 0000000 | 000000 |
200 | 330 Btu/hr. (80 mm), 260 Btu/hr. (100 mm), 220 Btu/hr. (120 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |
350 | 190 Btu/hr. (140 mm), 150 Btu/hr. (175 mm), 120 Btu/hr. (210 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 | 0000000 | 000000 |

Length, mm | Thickness, mm | Cooling Capacity (Installed Length) | Temperature Range, °F | Material | Working Fluid | Each | |
Sintered Wick | |||||||
---|---|---|---|---|---|---|---|
5.1 mm Width | |||||||
70 | 2.5 | 160 Btu/hr. (42 mm), 130 Btu/hr. (53 mm), 110 Btu/hr. (63 mm) | 90° to 245° | Copper | Water | 0000000 | 000000 |
100 | 2.5 | 110 Btu/hr. (60 mm), 90 Btu/hr. (75 mm), 70 Btu/hr. (90 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
150 | 2.5 | 70 Btu/hr. (90 mm), 60 Btu/hr. (113 mm), 50 Btu/hr. (135 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
200 | 2.5 | 50 Btu/hr. (120 mm), 40 Btu/hr. (150 mm), 30 Btu/hr. (180 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
6.44 mm Width | |||||||
70 | 3 | 220 Btu/hr. (42 mm), 170 Btu/hr. (53 mm), 150 Btu/hr. (63 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
100 | 3 | 150 Btu/hr. (60 mm), 120 Btu/hr. (75 mm), 100 Btu/hr. (90 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
150 | 3 | 100 Btu/hr. (90 mm), 80 Btu/hr. (113 mm), 60 Btu/hr. (135 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
200 | 3 | 70 Btu/hr. (120 mm), 60 Btu/hr. (150 mm), 50 Btu/hr. (180 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
9.45 mm Width | |||||||
75 | 5 | 380 Btu/hr. (45 mm), 310 Btu/hr. (56 mm), 250 Btu/hr. (68 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
150 | 5 | 190 Btu/hr. (90 mm), 150 Btu/hr. (113 mm), 120 Btu/hr. (135 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
200 | 5 | 140 Btu/hr. (120 mm), 110 Btu/hr. (150 mm), 90 Btu/hr. (180 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
350 | 5 | 80 Btu/hr. (210 mm), 60 Btu/hr. (263 mm), 50 Btu/hr. (315 mm) | 90° to 245° | Copper | Water | 0000000 | 00000 |
Constant-Wattage Heaters with Adjustable
Temperature Control for Pipes and Tubes


Turn the dial to control the percentage of time that these heaters cycle on, from 5% to 100%. Commonly used to thaw pipes, prevent valves from freezing, and heat beakers and flasks in labs, they're good for temporary and occasional use where rapid heating is required but precise temperature control is not.
Unlike self-regulating heaters, these continuously supply the same wattage regardless of the surrounding temperature. They do not have a temperature sensor, so you should only use them in areas where you can monitor them with a thermometer (sold separately). Do not use behind walls, underground, or in other difficult-to-access areas.
With a rubber coating, these heaters are both moisture and chemical resistant. Install them onto surfaces that are free of dirt, grease, and rough edges using fiberglass tape or heat-transfer putty. Do not use electrical tape, duct tape, metal bands, or wire. To prevent burnout, make sure they're in full contact with the surface and have no overlap. To prevent heat loss, wrap with fiberglass insulation.
Lg., ft. | Wattage, W | Watt Density, W/ft. | Thick. | Environment Temp. Range, °F | Cord Lg., ft. | Cable Cover Material | For Surface Material | For Use Outdoors | Current, A | Each | |
With Wire Leads—240V AC, Single Phase | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/2" Wd. | |||||||||||
2 | 72 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 0.3 | 0000000 | 0000000 |
4 | 144 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 0.6 | 0000000 | 000000 |
6 | 216 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 0.9 | 0000000 | 000000 |
8 | 288 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.2 | 0000000 | 000000 |
10 | 360 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.5 | 0000000 | 000000 |
12 | 432 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.8 | 00000000 | 000000 |
14 | 504 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.1 | 00000000 | 000000 |
16 | 576 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 00000000 | 000000 |
18 | 648 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 00000000 | 000000 |
20 | 720 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3 | 00000000 | 000000 |
1" Wd. | |||||||||||
2 | 144 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 0.6 | 0000000 | 000000 |
4 | 288 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.2 | 0000000 | 000000 |
6 | 432 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.8 | 0000000 | 000000 |
8 | 576 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 0000000 | 000000 |
10 | 720 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3 | 0000000 | 000000 |
12 | 864 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 00000000 | 000000 |
14 | 1,008 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.2 | 00000000 | 000000 |
16 | 1,152 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.8 | 00000000 | 000000 |
18 | 1,296 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 5.4 | 00000000 | 000000 |
20 | 1,440 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 6 | 0000000 | 000000 |
2" Wd. | |||||||||||
2 | 288 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.2 | 0000000 | 000000 |
4 | 576 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 0000000 | 000000 |
6 | 864 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 0000000 | 000000 |
8 | 1,152 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.8 | 0000000 | 000000 |
10 | 1,440 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 6 | 0000000 | 000000 |
3" Wd. | |||||||||||
2 | 432 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.8 | 0000000 | 000000 |
4 | 864 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 0000000 | 000000 |
6 | 1,296 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 5.4 | 0000000 | 000000 |
8 | 1,440 | 180 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 6 | 0000000 | 000000 |
10 | 1,800 | 180 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 7.5 | 0000000 | 000000 |
With Plug—120V AC, Single Phase | |||||||||||
1/2" Wd. | |||||||||||
2 | 72 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 0.6 | 0000000 | 000000 |
4 | 144 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.2 | 0000000 | 000000 |
6 | 216 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.8 | 0000000 | 000000 |
8 | 288 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 0000000 | 000000 |
10 | 360 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3 | 0000000 | 000000 |
12 | 432 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 00000000 | 000000 |
14 | 504 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.2 | 00000000 | 000000 |
16 | 576 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.8 | 00000000 | 000000 |
18 | 648 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 5.4 | 00000000 | 000000 |
20 | 720 | 36 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 6 | 00000000 | 000000 |
1" Wd. | |||||||||||
2 | 144 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 1.2 | 0000000 | 000000 |
4 | 288 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 0000000 | 000000 |
6 | 432 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 0000000 | 000000 |
8 | 576 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.8 | 0000000 | 000000 |
10 | 720 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 6 | 0000000 | 000000 |
12 | 864 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 7.2 | 00000000 | 000000 |
14 | 1,008 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 8.4 | 00000000 | 000000 |
16 | 1,152 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 9.6 | 00000000 | 000000 |
18 | 1,296 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 10.8 | 00000000 | 000000 |
20 | 1,440 | 72 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 12 | 0000000 | 000000 |
2" Wd. | |||||||||||
2 | 288 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 2.4 | 0000000 | 000000 |
4 | 576 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 4.8 | 0000000 | 000000 |
6 | 864 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 7.2 | 0000000 | 000000 |
8 | 1,152 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 9.6 | 0000000 | 000000 |
10 | 1,440 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 12 | 0000000 | 000000 |
3" Wd. | |||||||||||
2 | 432 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 3.6 | 0000000 | 000000 |
4 | 864 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 7.2 | 0000000 | 000000 |
6 | 1,296 | 216 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 10.8 | 0000000 | 000000 |
8 | 1,440 | 180 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 12 | 0000000 | 000000 |
10 | 1,440 | 144 | 3/16" | -30° to 450° | 6 | Rubber | Metal | No | 12 | 0000000 | 000000 |
Constant-Wattage Heaters with Temperature Control for Pipes and Tubes


A nonadjustable thermostat turns these heaters on when the temperature drops below 38° F and turns them off when the temperature reaches 45° F. Often used to maintain liquid temperature and viscosity and provide freeze protection in pipe and tube systems, they supply the same wattage regardless of the surrounding temperature and are less prone to power surges than self-regulating heaters. To prevent burnout, they should be installed straight along pipes and tubes; they must not be overlapped or spiraled and must be in full contact with the surface being heated. All are rated for outdoor use. The plastic cable cover provides corrosion resistance and durability. Heaters have a plug with an indicator light that shows when the system has power.
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Lg., ft. | Wattage, W | Watt Density, W/ft. | Current, A | Wd. | Thick. | Environment Temp. Range, °F | For Pipe Dia. | NEMA Style | Cord Lg., ft. | Cable Cover Material | For Surface Material | For Use Outdoors | Each | |
120V AC, Single Phase | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 21 | 7 | 0.2 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 000000 |
6 | 42 | 7 | 0.4 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
9 | 63 | 7 | 0.5 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
12 | 84 | 7 | 0.7 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
15 | 105 | 7 | 0.9 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
18 | 126 | 7 | 1.1 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
24 | 168 | 7 | 1.4 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
30 | 210 | 7 | 1.8 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
40 | 280 | 7 | 2.3 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
60 | 420 | 7 | 3.5 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
80 | 560 | 7 | 4.7 | 1/2" | 3/8" | -40° to 155° | 3/4" to 1 1/2" | 5-15 | 2 | Plastic | Metal, Plastic | Yes | 0000000 | 00000 |
Constant-Wattage Heaters for Pipes and Tubes



Since these heaters continually supply the same wattage regardless of the surrounding temperature, they’re less prone to power surges than self-regulating heaters. All require a temperature switch or controller (sold separately) to regulate heat output. They’re often used to maintain liquid temperature and viscosity and provide freeze protection in pipe and tube systems. To prevent burnout, heaters must not be overlapped and must be in full contact with the surface being heated. All have a plastic cable cover for corrosion resistance and durability. They are FM approved for hazardous locations. A power-connection/termination kit (sold separately) is required.
Power-connection/termination kit (sold separately) includes a junction box and a three-point DIN-mount terminal block. It also includes adhesive, an end cap, and a power-connection cover.
Termination kit (sold separately) includes adhesive, an end cap, and a power-connection cover.
LED termination kit (sold separately) has a high-visibility green LED to indicate when the heater is on. It also includes adhesive, an end cap, and a power-connection cover.
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Per Ft. | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Watt Density, W/ft. | Wd. | Thick. | Max. Lg., ft. | Environment Temp. Range, °F | Wire Connection Type | Cable Cover Material | For Surface Material | Environment | For Use Outdoors | 1-99 | 100-Up | |
150° F Max. Heat Output | ||||||||||||
120V AC, Single Phase | ||||||||||||
2.5 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 000000 | 00000 |
5 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 0000 |
8 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 0000 |
10 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 0000 |
240V AC, Single Phase | ||||||||||||
5 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 0000 |
480V AC, Single Phase | ||||||||||||
10 | 1/2" | 11/32" | 500 | -40° to 400° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
300° F Max. Heat Output | ||||||||||||
120V AC, Single Phase | ||||||||||||
10 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
15 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
240V AC, Single Phase | ||||||||||||
10 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
15 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
480V AC, Single Phase | ||||||||||||
10 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
15 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
20 | 1/2" | 11/32" | 500 | -60° to 500° | Wire Leads | Plastic | Metal | Hazardous Location | No | 00000000 | 00000 | 00000 |
Ultra-Flexible Constant-Wattage Heaters for Pipes and Tubes
Wrap the flexible fiber heating element around small-diameter pipes and tubes or pack it into tight spaces. Since these heaters supply the same wattage regardless of the surrounding temperature, they're less prone to power surges than self-regulating heaters. All require a temperature switch or controller (sold separately) to regulate heat output. They do not produce an electromagnetic field, so they can be used near electronics.
Heaters with a 2.1 mm ID connector can be used with an AC adapter (not included) to convert them to AC power.
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.

Lg., ft. | Wattage, W | Watt Density, W/ft. | Current, A | Wd. | Thick. | Environment Temp. Range, °F | Cable Cover Material | For Surface Material | Each | |
12V DC | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
1 | 3 | 3 | 0.3 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 000000 |
2 | 6 | 3 | 0.5 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
3 | 9 | 3 | 0.8 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
4 | 12 | 3 | 1 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
24V DC | ||||||||||
2 | 6 | 3 | 0.3 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
4 | 12 | 3 | 0.5 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
6 | 18 | 3 | 0.8 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
8 | 24 | 3 | 1 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
36V DC | ||||||||||
3 | 9 | 3 | 0.3 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
6 | 18 | 3 | 0.5 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
9 | 27 | 3 | 0.8 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |
12 | 36 | 3 | 1 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 |


Heaters | AC Adapters | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Lg., ft. | Wattage, W | Watt Density, W/ft. | Current, A | Wd. | Thick. | Environment Temp. Range, °F | Cable Cover Material | For Surface Material | Each | Each | ||
12V DC | ||||||||||||
1 | 3 | 3 | 0.3 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 000000 | 00000000 | 00000 |
2 | 6 | 3 | 0.5 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 0000 |
3 | 9 | 3 | 0.8 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
4 | 12 | 3 | 1 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
24V DC | ||||||||||||
2 | 6 | 3 | 0.3 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
4 | 12 | 3 | 0.5 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
6 | 18 | 3 | 0.8 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
8 | 24 | 3 | 1 | 0.12" | 0.06" | -30° to 220° | Polymer-Based Fiber | Metal, Plastic | 0000000 | 00000 | 00000000 | 00000 |
Self-Regulating Heaters for Pipes and Tubes




Also known as self-regulating heat cable, these heaters automatically adjust heat output in response to surface and surrounding temperatures without the need for a separate temperature-control device. They’re often used to maintain liquid temperature and viscosity and provide freeze protection in pipe and tube systems. Heaters can be overlapped without creating hot spots or risking burnout. All require a power-connection/termination kit (sold separately).
Heaters with a plastic cable cover are rated for use in hazardous locations. They are also more corrosion resistant and durable than heaters without a cable cover.
Power-connection/termination kits (sold separately) include a junction box and a three-point DIN-mount terminal. They also include adhesive, an end cap, and a power-connection cover.
Termination kits (sold separately) include adhesive, an end cap, and a power-connection cover.
LED termination kits (sold separately) have a high-visibility green LED to indicate when the heater is on. They also include adhesive, an end cap, and a power-connection cover.
Splice kits (sold separately) include adhesive, splice-connection covers, and wire-splicing connectors.
T-splice kits (sold separately) include adhesive, splice-connection covers, and wire-splicing connectors.
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Per Ft. | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Watt Density, W/ft. | Wd. | Thick. | Max. Lg., ft. | Environment Temp. Range, °F | Wire Connection Type | For Surface Material | Environment | NEC Hazardous Location Temp. Classification | For Use Outdoors | 1-99 | 100-Up | |
Without Cable Cover | ||||||||||||
3 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 00000 | 00000 |
5 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 0000 | 0000 |
8 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 0000 | 0000 |
10 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 00000 | 0000 |
With Plastic Cable Cover | ||||||||||||
3 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T6 (185° F) | No | 0000000 | 0000 | 0000 |
5 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T6 (185° F) | No | 0000000 | 00000 | 0000 |
8 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T6 (185° F) | No | 0000000 | 00000 | 0000 |
10 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T5 (212° F) | No | 0000000 | 00000 | 0000 |
Per Ft. | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Watt Density, W/ft. | Wd. | Thick. | Max. Lg., ft. | Environment Temp. Range, °F | Wire Connection Type | For Surface Material | Environment | NEC Hazardous Location Temp. Classification | For Use Outdoors | 1-99 | 100-Up | |
Without Cable Cover | ||||||||||||
3 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 00000 | 00000 |
5 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 0000 | 0000 |
8 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 0000 | 0000 |
10 | 1/2" | 3/16" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | __ | __ | No | 0000000 | 00000 | 0000 |
With Plastic Cable Cover | ||||||||||||
8 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T6 (185° F) | No | 0000000 | 00000 | 00000 |
10 | 9/16" | 1/4" | 500 | -60° to 185° | Wire Leads | Metal, Plastic | Hazardous Location | T5 (212° F) | No | 0000000 | 00000 | 00000 |
Per Ft. | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Watt Density, W/ft. | Wd. | Thick. | Max. Lg., ft. | Environment Temp. Range, °F | Wire Connection Type | For Surface Material | Environment | NEC Hazardous Location Temp. Classification | For Use Outdoors | 1-99 | 100-Up | |
With Plastic Cable Cover | ||||||||||||
9 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T3 (392° F) | No | 00000000 | 000000 | 000000 |
12 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T3 (392° F) | No | 00000000 | 00000 | 00000 |
15 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T2D (419° F) | No | 00000000 | 00000 | 00000 |
20 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T2D (419° F) | No | 00000000 | 00000 | 00000 |
Per Ft. | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Watt Density, W/ft. | Wd. | Thick. | Max. Lg., ft. | Environment Temp. Range, °F | Wire Connection Type | For Surface Material | Environment | NEC Hazardous Location Temp. Classification | For Use Outdoors | 1-99 | 100-Up | |
With Plastic Cable Cover | ||||||||||||
12 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T3 (392° F) | No | 00000000 | 000000 | 000000 |
20 | 7/16" | 1/4" | 500 | -75° to 400° | Wire Leads | Metal, Plastic | Hazardous Location | T2C (446° F) | No | 00000000 | 00000 | 00000 |
Ready-to-Use Self-Regulating Heaters for Pipes and Tubes



There’s no need for power-connection kits with these finished lengths of cable. These heaters automatically adjust heat output in response to surface and surrounding temperatures without a separate temperature switch or controller. They’re often used to maintain liquid temperature and viscosity and provide freeze protection in pipe and tube systems. All are CSA certified for pipe freeze protection and are rated for outdoor use. Heaters can be overlapped without creating hot spots or risking burnout. A protective rubber cover provides corrosion resistance and durability.
Heaters with a plug are also CSA certified for roof and gutter de-icing applications. The plug has an indicator light that shows when the system has power.
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Lg., ft. | Wattage, W | Watt Density, W/ft. | Wd. | Thick. | Environment Temp. Range, °F | Cord Lg., ft. | Cable Cover Material | For Surface Material | For Use Outdoors | Current, A | Each | |
6 | 36 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 0.2 | 0000000 | 0000000 |
12 | 72 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 0.3 | 0000000 | 000000 |
18 | 108 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 0.5 | 0000000 | 000000 |
24 | 144 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 0.6 | 0000000 | 000000 |
Lg., ft. | Wattage, W | Watt Density, W/ft. | Wd. | Thick. | Environment Temp. Range, °F | Cord Lg., ft. | Cable Cover Material | For Surface Material | For Use Outdoors | NEMA Style | Current, A | Each | |
6 | 36 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 0.3 | 0000000 | 0000000 |
12 | 72 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 0.6 | 0000000 | 000000 |
18 | 108 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 0.9 | 0000000 | 000000 |
24 | 144 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 1.2 | 0000000 | 000000 |
50 | 300 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 2.5 | 0000000 | 000000 |
75 | 450 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 3.8 | 0000000 | 000000 |
100 | 600 | 6 | 7/16" | 1/4" | -40° to 150° | 6 | Rubber | Metal, Plastic | Yes | 5-15 | 5 | 0000000 | 000000 |
High-Temperature Heaters for Pipes and Tubes


With a maximum heat output of 900° F, these heaters are often used for thawing frozen pipes and rapid spot heating. They supply the same wattage regardless of the surrounding temperature, so they're less prone to power surges than self-regulating heaters. To prevent burnout, heaters must not be overlapped and must be in full contact with the surface being heated.
Heaters with wire leads require a temperature switch or controller for regulating heat output.
Heaters with a plug require a power controller (sold separately).
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Lg. | Wattage, W | Watt Density, W/ft. | Current, A | Cable Cover Material | For Surface Material | For Use Outdoors | Thick. | Environment Temp. Range, °F | Each | |
With Wire Leads | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
120V AC, Single Phase | ||||||||||
6" | 25 | 50 | 0.2 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 000000 |
12" | 50 | 50 | 0.4 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 00000 |
24" | 100 | 50 | 0.8 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 00000 |
36" | 125 | 41.5 | 1 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 00000 |
60" | 250 | 50 | 2.1 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 00000 |
96" | 400 | 50 | 3.3 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 00000 |
120" | 500 | 50 | 4.2 | Fiberglass | Metal | No | 0.17" | -100° to 900° | 0000000 | 000000 |
With Plug | ||||||||||
120V AC, Single Phase | ||||||||||
8" | 35 | 52.5 | 0.3 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
12" | 50 | 50 | 0.4 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
24" | 100 | 50 | 0.8 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
36" | 125 | 41.5 | 1 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
60" | 250 | 50 | 2.1 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
96" | 400 | 50 | 3.3 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
120" | 500 | 50 | 4.2 | Fiberglass | Metal | No | 0.3" | -50° to 900° | 0000000 | 000000 |
Power Controller for Heaters with Plug | 000000 | Each | 000000 |
Ultra-High Temperature Heaters for Pipes and Tubes


For demanding applications such as hot-melt transfer pipes, these heaters have a maximum heat output of 1400° F. They supply the same wattage regardless of the surrounding temperature, so they're less prone to power surges than self-regulating heaters. All require a temperature switch or controller (sold separately) for regulating heat output. To prevent burnout, heaters must not be overlapped and must be in full contact with the surface being heated.
Heaters with a plug require a power controller (sold separately).
Note: Only install these heaters in accessible locations; do not install them behind walls, underground, or in other difficult-to-access areas. Use fiberglass tape or heat-transfer putty to install them directly on surfaces that are free of dirt, grease, and rough edges. Do not use electrical tape, duct tape, metal bands, or wire. To prevent heat loss and protect heaters from moisture and corrosion, wrap them with fiberglass insulation.
Lg., ft. | Wattage, W | Watt Density, W/ft. | Current, A | Wd. | Thick. | Environment Temp. Range, °F | Cable Cover Material | For Surface Material | For Use Outdoors | Each | |
With Wire Leads | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
120V AC, Single Phase | |||||||||||
2 | 39 | 19.5 | 0.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
2 | 104 | 52 | 0.9 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
2 | 156 | 78 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 78 | 19.5 | 0.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 208 | 52 | 1.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 312 | 78 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 117 | 19.5 | 1 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 312 | 52 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 468 | 78 | 3.9 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
8 | 156 | 19.5 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 416 | 52 | 3.5 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 624 | 78 | 5.2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 195 | 19.5 | 1.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 520 | 52 | 4.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
12 | 234 | 19.5 | 2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
16 | 312 | 19.5 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
240V AC, Single Phase | |||||||||||
2 | 39 | 19.5 | 0.2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
2 | 104 | 52 | 0.4 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
2 | 156 | 78 | 0.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 78 | 19.5 | 0.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 208 | 52 | 0.9 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 312 | 78 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 117 | 19.5 | 0.5 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 312 | 52 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 468 | 78 | 2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
8 | 156 | 19.5 | 0.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 416 | 52 | 1.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 624 | 78 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 195 | 19.5 | 0.8 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 520 | 52 | 2.2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
12 | 234 | 19.5 | 1 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
16 | 312 | 19.5 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
With Plug | |||||||||||
120V AC, Single Phase | |||||||||||
2 | 39 | 19.5 | 0.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
2 | 104 | 52 | 0.9 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
2 | 156 | 78 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 78 | 19.5 | 0.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 208 | 52 | 1.7 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
4 | 312 | 78 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 117 | 19.5 | 1 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 312 | 52 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
6 | 468 | 78 | 3.9 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 00000 |
8 | 156 | 19.5 | 1.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 416 | 52 | 3.5 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
8 | 624 | 78 | 5.2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 195 | 19.5 | 1.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
10 | 520 | 52 | 4.3 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
12 | 234 | 19.5 | 2 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
16 | 312 | 19.5 | 2.6 | 1/2" | 1/8" | -60° to 1400° | Fiberglass | Ceramic, Glass, Metal | No | 00000000 | 000000 |
Power Controller for Heaters with Plug | 000000 | Each | 000000 |
Multisize Conduit and Pipe Bending Blankets

Heat PVC conduit and pipe, then manually bend it to your desired angle. This electric blanket wraps around your workpiece and secures with a hook-and-loop strap.
For Rigid Conduit Trade Size | For Pipe Size | For Use On | Material | Lg. | Wd. | Electrical Connection Type | Plug Type | Voltage | Cord Lg., ft. | Each | |
1/2, 3/4, 1, 1 1/4, 1 1/2 | 1/2, 3/4, 1, 1 1/4, 1 1/2 | Plastic | Silicone Rubber/Vinyl Plastic | 13" | 8 1/4" | Plug | Two Prong | 120V AC | 8 | 0000000 | 0000000 |