About Exhaust Fans
More
About Sound Levels
Measured in decibels (dB), volume ratings indicate how much noise equipment makes. Some common volume levels include a whisper @ 20 dB, a refrigerator @ 40 dB, a conversation @ 60 dB, and a light machine shop @ 90 dB. OSHA recommends hearing protection for exposure to 80 dB and greater.
Light Duty Direct-Drive Wall-Mount Exhaust Fans with Louvers

These light duty fans are designed for use without duct. They come complete with a movable-blade louver. The louvers are gravity operated so they open only when air flows through them, which prevents backdrafts. Direct-drive fans have fewer moving parts than belt-drive fans for less maintenance. Use these fans to draw stagnant and humid air out of a room or area. All have a totally enclosed motor enclosure, which can be used in dirty, dusty, and damp environments.
For technical drawings and 3-D models, click on a part number.
For Opening | Overall | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Blade Dia. | Airflow, cfm | Motor Speed, rpm | No. of Speeds | Power, hp | Ht. | Wd. | Ht. | Wd. | Dp. | Max. Ambient Temperature | Control Type | Frame Material | Blade Material | Mount. Fasteners Included | Mount. Hole Dia. | Specifications Met | Each | |
120V AC, Single Phase—Hardwire | ||||||||||||||||||
10" | 680 | 1,560 | 3 | 1/12 | 10 1/2" | 10 1/2" | 13" | 13" | 8 1/8" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 0000000 |
12" | 825 | 1,560 | 3 | 1/12 | 12 1/2" | 12 1/2" | 15" | 15" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
16" | 2,100 | 1,660 | 3 | 1/8 | 16 1/2" | 16 1/2" | 19" | 19" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
18" | 2,300 | 1,660 | 3 | 1/8 | 18 1/2" | 18 1/2" | 21" | 21" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
20" | 2,925 | 1,140 | 2 | 1/4 | 20" | 20" | 23" | 23" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
24" | 3,400 | 1,140 | 2 | 1/4 | 24 1/2" | 24 1/2" | 27" | 27" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
30" | 3,950 | 1,140 | 2 | 1/4 | 30 1/2" | 30 1/2" | 33" | 33" | 9 1/2" | 100° F | Pull Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
230/460V AC, Three Phase—Hardwire | ||||||||||||||||||
24" | 3,950 | 1,720 | Variable | 1/2 | 24 1/2" | 24 1/2" | 28" | 28" | 17" | 100° F | Knob, On-Off Switch | Steel | Aluminum | No | 1/4" | UL Recognized Component | 00000000 | 000000 |
Direct-Drive Wall-Mount Exhaust Fans with Louvers
These fans come complete with a movable-blade louver. The louvers are gravity operated so they open only when air flows through them, which prevents backdrafts. Direct-drive fans have fewer moving parts than belt-drive fans for less maintenance. Use these fans to draw stagnant and humid air out of a room or area. All have an open dripproof motor enclosure for relatively clean, dry, indoor locations. They also have a wire mesh inlet guard to protect the fan from debris.
Fans that cannot be sold to California are restricted by local energy efficiency requirements.
For technical drawings and 3-D models, click on a part number.

For Opening | Overall | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Blade Dia. | Airflow, cfm | Volume | Motor Speed, rpm | No. of Speeds | Power, hp | Ht. | Wd. | Ht. | Wd. | Dp. | Housing Material | Frame Material | Blade Material | Specifications Met | Cannot Be Sold To | Each | |
120V AC, Single Phase—Hardwire | |||||||||||||||||
10" | 870 | 56 dBA @ 5 ft. | 1,550 | 1 | 1/20 | 17 1/4" | 17 1/4" | 19 1/2" | 19 1/2" | 20 3/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 0000000 |
12" | 1,500 | 60 dBA @ 5 ft. | 1,550 | 1 | 1/8 | 17 1/4" | 17 1/4" | 19 1/2" | 19 1/2" | 20 3/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 000000 |
16" | 2,500 | 61 dBA @ 5 ft. | 1,300 | 1 | 1/2 | 21 1/4" | 21 1/4" | 23 1/2" | 23 1/2" | 25 1/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 00000000 |
18" | 3,800 | 65 dBA @ 5 ft. | 1,300 | 1 | 3/4 | 25 1/4" | 25 1/4" | 27 1/2" | 27 1/2" | 26 1/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 00000000 |
24" | 6,600 | 67 dBA @ 5 ft. | 1,075 | 1 | 3/4 | 31 1/4" | 31 1/4" | 33 1/2" | 33 1/2" | 30 1/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 00000000 |
208-230/460V AC, Three Phase—Hardwire | |||||||||||||||||
24" | 5,200 | 69 dBA @ 5 ft. | 1,125 | 1 | 1/2 | 31 1/4" | 31 1/4" | 33 1/2" | 33 1/2" | 30 1/4" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | __ | 00000000 | 00000000 |
230/460V AC, Three Phase—Hardwire | |||||||||||||||||
30" | 8,400 | 74 dBA @ 5 ft. | 1,125 | 1 | 1 | 37 1/4" | 37 1/4" | 39 1/2" | 39 1/2" | 27 1/2" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | CA | 00000000 | 00000000 |
36" | 12,300 | 74 dBA @ 5 ft. | 850 | 1 | 1 1/2 | 43 1/4" | 43 1/4" | 45 1/2" | 45 1/2" | 31 1/2" | Steel | Galvanized Steel | Aluminum | C-UL Listed, UL Listed | CA | 00000000 | 00000000 |
Corrosion-Resistant Direct-Drive Wall-Mount Exhaust Fans with Louvers

Rust won't be a problem with the durable plastic housing and louvers on these fans. The fans come complete with a movable-blade louver. The louvers are gravity operated so they open only when air flows through them, which prevents backdrafts. Direct-drive fans have fewer moving parts than belt-drive fans for less maintenance. Use these fans to draw stagnant and humid air out of a room or area. All have a totally enclosed motor enclosure, which can be used in dirty, dusty, and damp environments.
For technical drawings and 3-D models, click on a part number.
For Opening | Overall | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Blade Dia. | Airflow, cfm | Motor Speed, rpm | No. of Speeds | Power, hp | Ht. | Wd. | Ht. | Wd. | Dp. | Max. Ambient Temperature | Housing Material | Blade Material | Each | |
120/230V AC, Single Phase—Hardwire | ||||||||||||||
12" | 1,300 | 1,700 | 1 | 1/3 | 17 1/2" | 18 1/2" | 21 1/4" | 20 3/4" | 20 5/8" | 104° F | Fiberglass | Polypropylene Plastic | 0000000 | 0000000 |
16" | 2,400 | 1,725 | 1 | 1/3 | 21 1/2" | 23" | 24 5/8" | 24 1/8" | 23" | 104° F | Fiberglass | Polypropylene Plastic | 0000000 | 000000 |
20" | 3,100 | 1,700 | 1 | 1/3 | 25 3/4" | 25 3/4" | 28 1/4" | 28 3/4" | 25 1/2" | 104° F | Fiberglass | Polypropylene Plastic | 0000000 | 000000 |
24" | 4,700 | 1,700 | 1 | 1/2 | 31 1/2" | 31 1/2" | 34 3/8" | 34 1/2" | 27 1/2" | 104° F | Fiberglass | Polypropylene Plastic | 0000000 | 000000 |
Belt-Drive Wall-Mount Exhaust Fans with Louvers
These fans come complete with a movable-blade louver. The louvers are gravity operated so they open only when air flows through them, which prevents backdrafts. Belt-drive fans are quieter and have a longer life span than direct-drive fans because components can be replaced if worn or damaged. Use these fans to draw stagnant and humid air out of a room or area.
Fans with an open dripproof motor enclosure are for relatively clean, dry, indoor locations. Fans with a totally enclosed motor enclosure can be used in dirty, dusty, and damp environments.
For technical drawings and 3-D models, click on a part number.

For Opening | Overall | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Blade Dia. | Airflow, cfm | Volume | Motor Speed, rpm | No. of Speeds | Power, hp | Ht. | Wd. | Ht. | Wd. | Dp. | Wt., lbs. | Max. Ambient Temperature | Housing Material | Frame Material | Blade Material | Mount. Fasteners Included | Mount. Hole Dia. | Each | |
Open Dripproof Motor Enclosure | |||||||||||||||||||
120V AC, Single Phase—Hardwire | |||||||||||||||||||
30" | 6,000 | 55 dB @ 5 ft. | 550 | 1 | 1/2 | 37" | 37" | 36 1/2" | 36 1/2" | 19" | 152 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 000000000 |
36" | 8,100 | 53 dB @ 5 ft. | 400 | 1 | 1/2 | 43" | 43" | 42 1/2" | 42 1/2" | 19" | 121 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
42" | 11,000 | 57 dB @ 5 ft. | 400 | 1 | 3/4 | 49" | 49" | 48 1/2" | 48 1/2" | 19" | 270 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
48" | 14,900 | 57 dB @ 5 ft. | 350 | 1 | 1 | 55" | 55" | 54 1/2" | 54 1/2" | 19" | 266 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
Totally Enclosed Motor Enclosure | |||||||||||||||||||
230/460V AC, Three Phase—Hardwire | |||||||||||||||||||
30" | 6,000 | 55 dB @ 5 ft. | 550 | 1 | 1/2 | 37" | 37" | 36 1/2" | 36 1/2" | 25" | 153 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
36" | 8,100 | 53 dB @ 5 ft. | 400 | 1 | 1/2 | 43" | 43" | 42 1/2" | 42 1/2" | 25" | 225 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
42" | 11,000 | 57 dB @ 5 ft. | 400 | 1 | 3/4 | 49" | 49" | 48 1/2" | 48 1/2" | 25" | 250 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
48" | 14,900 | 57 dB @ 5 ft. | 350 | 1 | 1 | 55" | 55" | 54 1/2" | 54 1/2" | 25" | 324 | 104° F | Steel | Steel | Steel | No | 3/16" | 0000000 | 00000000 |
Exterior-Wall-Mount Exhaust Fans



Good when you don't have room to mount an exhaust fan inside your facility, these fans attach to an outside wall and work with or without duct. To use with duct, add an angle ring (not included). All fans are direct-drive fans and have fewer moving parts than belt-drive fans for less maintenance. Use them to draw stagnant and humid air out of a room or area.
120V AC fans have an open dripproof motor enclosure for relatively clean, dry, indoor locations.
120/230V AC fan has a totally enclosed fan cooled motor for use in dirty, dusty, and damp environments
Note: Airflow depends on the resistance created by louvers, filters, and ductwork in your system. This resistance, known as static pressure (SP), is measured in inches of water.
Grilles (sold separately) have fixed blades.
Louvers (sold separately) are gravity operated. The blades open when air flows and close when it stops, preventing backdrafts.
For technical drawings and 3-D models, click on a part number.
Fans | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
For Opening | Overall | Grilles | Louvers | ||||||||||||||
Blade Dia. | Airflow @ Static Pressure | Volume | Motor Speed, rpm | Power, hp | Dia. | Ht. | Wd. | Dia. | Dp. | Max. Ambient Temperature | Specifications Met | Each | Each | Each | |||
120V AC, Single Phase—Hardwire | |||||||||||||||||
7" | 190 cfm @ 0 in. of H₂O | 39 dBA @ 15 ft. | 1,050 | 1/25 | 8" | 8" | 8" | 17 1/8" | 13" | 180° F | C-UL Listed UL Listed | 000000 | 0000000 | 0000000 | 000000 | 0000000 | 000000 |
10" | 250 cfm @ 1/4 in. of H₂O 550 cfm @ 0 in. of H₂O | 42 dBA @ 15 ft. | 1,050 | 1/25 | 10" | 10" | 10" | 21 1/8" | 16" | 180° F | C-UL Listed UL Listed | 000000 | 000000 | 0000000 | 00000 | 0000000 | 00000 |
13" | 1,400 cfm @ 1/4 in. of H₂O 1,600 cfm @ 0 in. of H₂O | 49 dBA @ 15 ft. | 1,075 | 1/6 | 12" | 12" | 12" | 30 3/16" | 28 3/4" | 180° F | C-UL Listed UL Listed | 000000 | 00000000 | 0000000 | 00000 | 0000000 | 00000 |
16" | 2,400 cfm @ 1/4 in. of H₂O 2,800 cfm @ 0 in. of H₂O | 56 dBA @ 15 ft. | 1,075 | 1/3 | 14" | 16" | 16" | 34 11/16" | 30 7/8" | 180° F | C-UL Listed UL Listed | 000000 | 00000000 | 0000000 | 000000 | 0000000 | 00000 |
120/230V AC, Single Phase—Hardwire | |||||||||||||||||
18" | 4,000 cfm @ 1/4 in. of H₂O 4,300 cfm @ 0 in. of H₂O | 58 dBA @ 15 ft. | 1,125 | 3/4 | 20" | 20" | 20" | 39 7/16" | 35 5/8" | 180° F | C-UL Listed UL Listed | 0000000 | 00000000 | 0000000 | 000000 | 0000000 | 000000 |