    16 Products

    High-Power Circuit Breakers

    Image of Product. Shunt Trip. Front orientation. Circuit Breakers. High-Power Circuit Breakers.

    Shunt

    Trip

    Image of Product. Circuit Breaker. Front orientation. Circuit Breakers. High-Power Circuit Breakers.

    Circuit

    Breaker

    Image of Product. Undervoltage Trip. Front orientation. Circuit Breakers. High-Power Circuit Breakers.

    Undervoltage

    Trip

    Protect an area of a facility that has high-powered equipment. These circuit breakers are also known as molded case circuit breakers. Because these breakers are thermal-magnetic, they trip two ways. They either trip when heat is generated slowly by consistent low-level overload current, or they trip quickly when the magnetic coil senses a high-current short circuit. A switch lets you adjust when these breakers magnetically trip, so you don't need to replace them as your application changes. These breakers have internal accessory slots to fit shunt trips, auxiliary contacts, and undervoltage trips, saving space in your setup.
    Undervoltage trips protect equipment from operating with less than their intended voltage by tripping a circuit breaker when the supply voltage drops below a set level. 30 amp to 250 amp breakers can only have one shunt trip or undervoltage trip installed. 400 amp to 600 amp breakers can accommodate one shunt trip and one undervoltage trip at the same time.
    Shunt trips receive a signal from equipment to trip your circuit breaker in situations other than overload or short circuit conditions. For example, use them with a smoke detector to shut off power to a system in the event of a fire. 30 amp to 250 amp breakers can only have one shunt trip or undervoltage trip installed. 400 amp to 600 amp breakers can accommodate one shunt trip and one undervoltage trip at the same time.
    UL 489—They meet UL 489 requirements for branch circuit protection.
    Breakthrough Current @ Voltage—Breakthrough current is the maximum current that the circuit breaker can safely stop in the event of a short circuit.
    Mounting
    Holes
    Screw On
    Current,
    A
    Voltage
    Freq., Hz
    Breakthrough Current @ Voltage
    Inrush Current Setting, amp
    For DIN
    Rail Size, mm
    Mounting
    Location
    No.
    of
    Dia.
    Mounting Fasteners
    Included
    Wire
    Connection
    Ht.
    Wd.
    Dp.
    Temp. Range,
    ° F
    Specs. Met
    Certification
    Each
    3 Poles—Toggle-Switch Style
     
    Thermal/Magnetic
    30600V DC
    480V AC
    600YV AC/347V AC
    50/6065,000 amp @ 240V AC
    25,000 amp @ 480V AC
    14,000 amp @ 600V AC
    14,000 amp @ 125V DC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    150; 180; 210; 240; 270; 30035DIN Rail411/64"YesTab5.5"3"3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N110000000
    60600V DC
    480V AC
    600YV AC/347V AC
    50/6065,000 amp @ 240V AC
    25,000 amp @ 480V AC
    14,000 amp @ 600V AC
    14,000 amp @ 125V DC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    300; 360; 420; 480; 540; 60035DIN Rail411/64"YesTab5.5"3"3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N12000000
    100600V DC
    480V AC
    600YV AC/347V AC
    50/6065,000 amp @ 240V AC
    25,000 amp @ 480V AC
    14,000 amp @ 600V AC
    14,000 amp @ 125V DC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    500; 600; 700; 800; 900; 1,00035DIN Rail411/64"YesTab5.5"3"3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N13000000
    125600V DC
    480V AC
    600YV AC/347V AC
    50/6065,000 amp @ 240V AC
    25,000 amp @ 480V AC
    14,000 amp @ 600V AC
    14,000 amp @ 125V DC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    625; 750; 875; 1,000; 1,125; 1,25035DIN Rail411/64"YesTab5.5"3"3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1400000000
    150600V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    750; 900; 1,050; 1,200; 1,350; 1,50043/16"YesTab7.3"4.1"3.3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1500000000
    200600V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    1,000; 1,200; 1,400; 1,600; 1,800; 2,00043/16"YesTab7.3"4.1"3.3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1600000000
    225600V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    1,125; 1,350; 1,575; 1,800; 2,025; 2,25043/16"YesTab7.3"4.1"3.3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1700000000
    250600V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 250V DC
    50,000 amp @ 500V DC
    50,000 amp @ 600V DC
    1,250; 1,500; 1,750; 2,000; 2,250; 2,50043/16"YesTab7.3"4.1"3.3"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1800000000
    400750V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 600V DC
    10,000 amp @ 750V DC
    2,000; 2,400; 2,800; 3,200; 3,600; 4,00047/32"YesTab9.8"5.4"5.4"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N1900000000
    600 750V DC
    600V AC
    600YV AC/347V AC
    50/6085,000 amp @ 240V AC
    35,000 amp @ 480V AC
    18,000 amp @ 600V AC
    50,000 amp @ 600V DC
    10,000 amp @ 750V DC
    3,000; 3,600; 4,200; 4,800; 5,400; 6,00047/32"YesTab9.8"5.4"5.4"-10 to 155UL 489, IEC 60947-2, IEC 81346-2UL Listed, CE Marked
    4434N2100000000
     