Maximum Setpoint Maximum Setpoint |
---|
|
For Use With For Use With |
---|
|
Minimum Setpoint Minimum Setpoint |
---|
|
Switch Starting Position Switch Starting Position |
---|
|
Scale Scale |
---|
|
Maximum Pressure Maximum Pressure |
---|
|
|
Housing Material Housing Material |
---|
|
Environmental Rating Environmental Rating |
---|
DFARS (Defense Acquisition Regulations Supplement) DFARS (Defense AcquisitionRegulations Supplement) |
---|
RoHS (Restriction of Hazardous Substances) RoHS (Restriction ofHazardous Substances) |
---|
|
REACH (Registration, Evaluation, Authorization and Restriction of Chemicals) REACH (Registration,Evaluation, Authorization and Restriction of Chemicals) |
---|
|
About Pressure Switches
More
Low Differential Pressure Switches

- For Use With: Air
- Connection Material: Aluminum
- Connection: NPT Female
- Switching Current: 15A
- Switching Voltage: 120V AC/240V AC/480V AC
Often used with ovens, dryers, and HVAC systems, these switches detect small differences in pressure. When the differential pressure exceeds your setpoint, the switch is activated. Use them to automate controls or activate an alarm in your process. Switches are single pole, double throw (SPDT), so they switch one circuit on or off. They can be wired normally open (NO) or normally closed (NC).
Temperature Range, °F | Conduit | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, in. of H2O | Approximate Difference Between Setpoint and Reset Point, in. of H2O | Max. Pressure, in. of H2O | Accuracy | Pipe Size | Environment | Process | For Trade Size | Connection Gender | Specifications Met | Each | |
Zinc-Plated Steel Housing | |||||||||||
0.07-0.15 | 0.04 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 000000 |
0.15-0.55 | 0.1 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 00000 |
0.4-1.6 | 0.16 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 00000 |
1.4-5 1/2 | 0.3 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 00000 |
3-11 3/4 | 0.4 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 00000 |
4-20 | 0.5 | 45 | ±3% | 1/8 | -30° to 180° | -30° to 180° | 7/8 | Female | CE Marked, CSA Certified, FM Approved, UL Recognized Component | 00000000 | 00000 |
Washdown Differential Pressure Switches with Dial Indicator

- For Use With: Air, Hydraulic Fluid, Water
- Connection Material: Brass
- Connection: NPT Female
- Switching Current: 0.25A
- Switching Voltage: 120V AC
Not only are these switches rated NEMA 4X for protection from dirt, washdowns, and corrosion, they also have an indicator for additional monitoring at the source of your application. Switches operate based on the difference in pressure between two process lines. When the differential pressure exceeds your setpoint, the switch is activated. Use them to automate controls or activate an alarm in your process. Switches are single pole, double throw (SPDT), so they switch one circuit on or off. They can be wired normally open (NO) or normally closed (NC).
Temperature Range, °F | Conduit | Lens | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, psi | Approximate Difference Between Setpoint and Reset Point, psi | Max. Pressure, psi | Accuracy | Pipe Size | Environment | Process | For Trade Size | Connection | Dia. | Material | Specifications Met | Each | |
Brass Housing | |||||||||||||
3-15 | 3 | 5,000 | ±2% | 1/4 | -40° to 175° | -40° to 175° | 1/2 | NPT Female | 3" | Glass | CSA Certified | 00000000 | 0000000 |
6-30 | 6 | 5,000 | ±2% | 1/4 | -40° to 175° | -40° to 175° | 1/2 | NPT Female | 3" | Glass | CSA Certified | 00000000 | 000000 |
10-50 | 10 | 5,000 | ±2% | 1/4 | -40° to 175° | -40° to 175° | 1/2 | NPT Female | 3" | Glass | CSA Certified | 00000000 | 000000 |
Differential Pressure Switches

- For Use With: Air, Hydraulic Fluid (Petroleum Based), Water
- Connection Material: Brass
- Connection: NPT Female
- Switching Current: 5A
- Switching Voltage: 120V AC/240V AC
These switches operate based on the difference in pressure between two process lines. When the differential pressure exceeds your setpoint, the switch is activated. Often used to indicate clogged filters, they are designed to automate controls or activate an alarm in your process. Switches are single pole, double throw (SPDT), so they switch one circuit on or off. They can be wired normally open (NO) or normally closed (NC). They are rated NEMA 4 to withstand washdowns, dust, and outdoor environments.
Temperature Range, °F | Conduit | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, psi | Approximate Difference Between Setpoint and Reset Point, psi | Max. Pressure, psi | Accuracy | Pipe Size | Environment | Process | For Trade Size | Connection Gender | Environmental Rating | Specifications Met | Each | |
300 Series Stainless Steel and Polyester Plastic Housing | ||||||||||||
1-10 | 0.75 | 150 | ±1% | 1/4 | 30° to 160° | 0° to 200° | 7/8 | Female | NEMA 4 | UL Listed, C-UL Listed, CE Marked | 00000000 | 0000000 |
4-45 | 1 | 150 | ±1% | 1/4 | 30° to 160° | 0° to 200° | 7/8 | Female | NEMA 4 | UL Listed, C-UL Listed, CE Marked | 00000000 | 000000 |
Washdown Differential Pressure Switches

- For Use With: Air, Hydraulic Fluid (Petroleum Based), Water
- Connection Material: Brass
- Connection: NPT Female
- Switching Current: 5A
- Switching Voltage: 120V AC/240V AC
These switches are rated NEMA 4 for protection from dirt and washdowns. They operate based on the difference in pressure between two process lines. When the differential pressure exceeds your setpoint, the switch is activated. Often used to indicate clogged filters, they are designed to automate controls or activate an alarm in your process. Switches are single pole, double throw (SPDT), so they switch one circuit on or off. They can be wired normally open (NO) or normally closed (NC).
Temperature Range, °F | Conduit | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, psi | Approximate Difference Between Setpoint and Reset Point, psi | Max. Pressure, psi | Accuracy | Pipe Size | Environment | Process | For Trade Size | Connection | Specifications Met | Each | |
300 Series Stainless Steel and Polyester Plastic Housing | |||||||||||
1-10 | 0.75 | 150 | ±1% | 1/4 | 30° to 160° | 0° to 200° | 7/8 | NPT Female | C-UL Listed, CE Marked, UL Listed | 00000000 | 0000000 |
4-45 | 1 | 150 | ±1% | 1/4 | 30° to 160° | 0° to 200° | 7/8 | NPT Female | C-UL Listed, CE Marked, UL Listed | 00000000 | 000000 |
Air-Pressure-Actuated HVAC Switches

Often used to detect clogged air filters and iced air conditioner coils, these switches sense small changes in pressure between two points in your duct.
Setpoint, in. of H2O | Accuracy, in. of H2O | Temperature Range, °F | Current | Electrical Connection Type | Switch Type | Max. Pressure, psi | Low Pressure Side Connection | High Pressure Side Inside Connection | High Pressure Side Outside Connection | Each | |
Diaphragm Sensor | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
0.05-5 | 0.025 | -40° to 165° | 2.9 A @ 240 V AC 5.8 A @ 120 V AC | Hardwire | SPDT | 1 | 1/8 NPT Female | 1/8 NPT Female | 1/2 NPSM | 000000 | 0000000 |
0.05-5 | 0.04 | -40° to 165° | 4.9 A @ 240 V AC 9.8 A @ 120 V AC | Hardwire | SPDT | 1 | 1/8 NPT Female | 1/8 NPT Female | 1/2 NPSM | 000000 | 000000 |
Airflow-Actuated HVAC Switches

Use this switch to sense changes in airflow velocity in duct. The paddle extends into the duct and actuates the switch when airflow reaches the setpoint. Switch is rated NEMA 3R for protection from dirt, falling liquids, and light splashing.
Paddle | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, fpm | Temperature Range, °F | Current | Electrical Connection Type | Switch Type | For Conduit Trade Size | Knockout Dia. | Material | Ht. | Wd. | For Use Outdoors | Environmental Rating | Specifications Met | Each | |
Paddle Sensor | ||||||||||||||
350-500 | 32° to 104° | 10 A @ 240 V AC 16 A @ 120 V AC | Screw Terminal | SPDT | 1/2 | 7/8" | Stainless Steel | 6 7/8" | 3 1/8" | Yes | IP43, NEMA 3R | UL Listed, C-UL Listed, CE Marked | 0000000 | 0000000 |